# IF-MIB
# Interface statistics using the IF-MIB
#
Type "if_octets"
Table true
Instance "IF-MIB::ifDescr"
Values "IF-MIB::ifInOctets" "IF-MIB::ifOutOctets"
Type "if_octets"
Table true
Instance "IF-MIB::ifName"
Values "IF-MIB::ifHCInOctets" "IF-MIB::ifHCOutOctets"
Type "if_packets"
Table true
Instance "IF-MIB::ifDescr"
Values "IF-MIB::ifInUcastPkts" "IF-MIB::ifOutUcastPkts"
Type "if_packets"
Table true
Instance "IF-MIB::ifName"
Values "IF-MIB::ifHCInUcastPkts" "IF-MIB::ifHCOutUcastPkts"
Type "if_errors"
Table true
Instance "IF-MIB::ifDescr"
Values "IF-MIB::ifInErrors" "IF-MIB::ifOutErrors"
Type "if_errors"
Table true
Instance "IF-MIB::ifName"
Values "IF-MIB::ifHCInErrors" "IF-MIB::ifHCOutErrors"
#
# UPS-MIB
# Statistics about your UPS using the UPS-MIB from the RFC1628.
#
# Battery branch
Type "timeleft"
Table false
Instance "battery"
Values ".1.3.6.1.2.1.33.1.2.3.0"
Type "percent"
Table false
Instance "charge-battery"
Values ".1.3.6.1.2.1.33.1.2.4.0"
Type "voltage"
Table false
Instance "battery"
Values ".1.3.6.1.2.1.33.1.2.5.0"
Scale 0.1
Type "current"
Table false
Instance "battery"
Values ".1.3.6.1.2.1.33.1.2.6.0"
Scale 0.1
Type "temperature"
Table false
Instance "battery"
Values ".1.3.6.1.2.1.33.1.2.7.0"
# Input branch
Type "frequency"
Table true
InstancePrefix "input"
Values ".1.3.6.1.2.1.33.1.3.3.1.2"
Scale 0.1
Type "voltage"
Table true
InstancePrefix "input"
Values ".1.3.6.1.2.1.33.1.3.3.1.3"
Type "current"
Table true
InstancePrefix "input"
Values ".1.3.6.1.2.1.33.1.3.3.1.4"
Scale 0.1
Type "power"
Table true
InstancePrefix "input"
Values ".1.3.6.1.2.1.33.1.3.3.1.5"
# Output branch
Type "frequency"
Table false
Instance "output"
Values ".1.3.6.1.2.1.33.1.4.2.0"
Scale 0.1
Type "voltage"
Table true
InstancePrefix "output"
Values ".1.3.6.1.2.1.33.1.4.4.1.2"
Type "current"
Table true
InstancePrefix "output"
Values ".1.3.6.1.2.1.33.1.4.4.1.3"
Scale 0.1
Type "power"
Table true
InstancePrefix "output"
Values ".1.3.6.1.2.1.33.1.4.4.1.4"
Type "percent"
Table true
InstancePrefix "load-output"
Values ".1.3.6.1.2.1.33.1.4.4.1.5"
# Bypass branch
Type "frequency"
Table false
Instance "output"
Values ".1.3.6.1.2.1.33.1.5.1.0"
Scale 0.1
Type "voltage"
Table true
InstancePrefix "bypass"
Values ".1.3.6.1.2.1.33.1.5.3.1.2"
Type "current"
Table true
InstancePrefix "bypass"
Values ".1.3.6.1.2.1.33.1.5.3.1.3"
Scale 0.1
Type "power"
Table true
InstancePrefix "bypass"
Values ".1.3.6.1.2.1.33.1.5.3.1.4"
# Special definitions for broken UPSes
Type "voltage"
Table false
Instance "battery"
Values ".1.3.6.1.2.1.33.1.2.5.0"
Type "current"
Table true
InstancePrefix "input"
Values ".1.3.6.1.2.1.33.1.3.3.1.4"
Type "current"
Table true
InstancePrefix "output"
Values ".1.3.6.1.2.1.33.1.4.4.1.3"
#
# Riello UPS
# Temperatures for UPSes by Riello,
#
Type "temperature"
Table false
Instance "system"
Values ".1.3.6.1.4.1.5491.1.51.1.5.4.0"
Type "temperature"
Table false
Instance "rectifier"
Values ".1.3.6.1.4.1.5491.1.51.1.5.5.0"
Type "temperature"
Table false
Instance "inverter"
Values ".1.3.6.1.4.1.5491.1.51.1.5.6.0"
#
# PowerPlus UPS, manufactured by Gamatronic, ,
# distributed in Germany by AdPoS,
#
# Global inputs
Type "voltage"
Table true
InstancePrefix "input"
Values ".1.3.6.1.4.1.6050.5.4.1.1.2"
Type "current"
Table true
InstancePrefix "input"
Values ".1.3.6.1.4.1.6050.5.4.1.1.3"
Type "power"
Table true
InstancePrefix "apparent-input"
Values ".1.3.6.1.4.1.6050.5.4.1.1.4"
Scale 100.0
Type "power"
Table true
InstancePrefix "active-input"
Values ".1.3.6.1.4.1.6050.5.4.1.1.5"
Scale 100.0
Type "percent"
Table true
InstancePrefix "performance_factor-input"
Values ".1.3.6.1.4.1.6050.5.4.1.1.6"
# Global outputs
Type "voltage"
Table true
InstancePrefix "output"
Values ".1.3.6.1.4.1.6050.5.5.1.1.2"
Type "current"
Table true
InstancePrefix "output"
Values ".1.3.6.1.4.1.6050.5.5.1.1.3"
Type "power"
Table true
InstancePrefix "apparent-output"
Values ".1.3.6.1.4.1.6050.5.5.1.1.4"
Scale 100.0
Type "power"
Table true
InstancePrefix "active-output"
Values ".1.3.6.1.4.1.6050.5.5.1.1.5"
Scale 100.0
Type "percent"
Table true
InstancePrefix "load_level-output"
Values ".1.3.6.1.4.1.6050.5.5.1.1.6"
Type "percent"
Table true
InstancePrefix "active_load_level-output"
Values ".1.3.6.1.4.1.6050.5.5.1.1.7"
Type "percent"
Table true
InstancePrefix "performance_factor-output"
Values ".1.3.6.1.4.1.6050.5.5.1.1.8"
# Global DC
Type "voltage"
Table false
Instance "dc_positive-global"
Values ".1.3.6.1.4.1.6050.5.6.1.0"
Type "voltage"
Table false
Instance "dc_negative-global"
Values ".1.3.6.1.4.1.6050.5.6.2.0"
Type "voltage"
Table false
Instance "dc_total-global"
Values ".1.3.6.1.4.1.6050.5.6.3.0"
#
# NetApp
# Some simple statistics of storage systems by NetApp.
#
Type "cpu"
Table false
Instance "system"
Values ".1.3.6.1.4.1.789.1.2.1.2.0"
Type "cpu"
Table false
Instance "idle"
Values ".1.3.6.1.4.1.789.1.2.1.4.0"
Type "if_octets"
Table false
Instance "net"
Values ".1.3.6.1.4.1.789.1.2.2.12.0" ".1.3.6.1.4.1.789.1.2.2.14.0"
#
# Juniper SSL
# Some stats of an SSL-appliance by Juniper.
#
Type "users"
Table false
Instance "web"
Values ".1.3.6.1.4.1.12532.2.0"
Type "users"
Table false
Instance "mail"
Values ".1.3.6.1.4.1.12532.3.0"
Type "percent"
Table false
Instance "logfull"
Values ".1.3.6.1.4.1.12532.1.0"
Type "percent"
Table false
Instance "diskfull"
Values ".1.3.6.1.4.1.12532.25.0"
#
# WuT
# Some thermometers and digital IO devices from WuT
#
#
Type "temperature"
Table true
Instance ".1.3.6.1.4.1.5040.1.2.6.3.2.1.1.2"
Values ".1.3.6.1.4.1.5040.1.2.6.1.4.1.1"
Scale 0.1
Type "temperature"
Table true
Instance ".1.3.6.1.4.1.5040.1.2.7.3.2.1.1.2"
Values ".1.3.6.1.4.1.5040.1.2.7.1.4.1.1"
Scale 0.1
Type "temperature"
Table true
Instance ".1.3.6.1.4.1.5040.1.2.8.3.2.1.1.2"
Values ".1.3.6.1.4.1.5040.1.2.8.1.4.1.1"
Scale 0.1
Type "temperature"
Table true
Instance ".1.3.6.1.4.1.5040.1.2.1.3.2.1.1.2"
Values ".1.3.6.1.4.1.5040.1.2.1.1.4.1.1"
Scale 0.1
Type "temperature"
Table true
Instance ".1.3.6.1.4.1.5040.1.2.2.3.2.1.1.2"
Values ".1.3.6.1.4.1.5040.1.2.2.1.4.1.1"
Scale 0.1
Type "temperature"
Table true
Instance ".1.3.6.1.4.1.5040.1.2.3.3.2.1.1.2"
Values ".1.3.6.1.4.1.5040.1.2.3.1.4.1.1"
Scale 0.1
#
# Infratec
# Rack monitoring devices by Infratec,
#
# Model H2-17
Type "temperature"
Table true
Instance ".1.3.6.1.4.1.4519.10.4.1.1.2"
Values ".1.3.6.1.4.1.4519.10.4.1.1.3"
Type "humidity"
Table true
Instance ".1.3.6.1.4.1.4519.10.5.1.1.2"
Values ".1.3.6.1.4.1.4519.10.5.1.1.3"
Type "voltage"
Table true
InstancePrefix "input"
Values ".1.3.6.1.4.1.4519.10.6.1.1.3"
# Model H2-30
Type "temperature"
Table true
Instance ".1.3.6.1.4.1.1909.10.4.1.1.2"
Values ".1.3.6.1.4.1.1909.10.4.1.1.3"
Type "humidity"
Table true
Instance ".1.3.6.1.4.1.1909.10.5.1.1.2"
Values ".1.3.6.1.4.1.1909.10.5.1.1.3"
Type "voltage"
Table true
InstancePrefix "input"
Values ".1.3.6.1.4.1.1909.10.6.1.1.3"
#
# Mikrotik RouterBoards
#
# Wireless statistics: station mode
tYPE "Bitrate"
Table true
InstancePrefix "st-tx-"
Instance ".1.3.6.1.4.1.14988.1.1.1.1.1.5"
Values ".1.3.6.1.4.1.14988.1.1.1.1.1.2"
Type "bitrate"
Table true
InstancePrefix "st-rx-"
Instance ".1.3.6.1.4.1.14988.1.1.1.1.1.5"
Values ".1.3.6.1.4.1.14988.1.1.1.1.1.3"
Type "signal_power"
Table true
InstancePrefix "st-"
Instance ".1.3.6.1.4.1.14988.1.1.1.1.1.5"
Values ".1.3.6.1.4.1.14988.1.1.1.1.1.4"
# Wireless statistics: AP mode / registration table
Type "signal_power"
Table true
InstancePrefix "ap-"
Instance ".1.3.6.1.4.1.14988.1.1.1.2.1.1"
Values ".1.3.6.1.4.1.14988.1.1.1.2.1.3"
Type "if_octets"
Table true
InstancePrefix "ap-"
Instance ".1.3.6.1.4.1.14988.1.1.1.2.1.1"
Values ".1.3.6.1.4.1.14988.1.1.1.2.1.5" ".1.3.6.1.4.1.14988.1.1.1.2.1.4"
Type "if_packets"
Table true
InstancePrefix "ap-"
Instance ".1.3.6.1.4.1.14988.1.1.1.2.1.1"
Values ".1.3.6.1.4.1.14988.1.1.1.2.1.7" ".1.3.6.1.4.1.14988.1.1.1.2.1.6"
Type "bitrate"
Table true
InstancePrefix "ap-tx-"
Instance ".1.3.6.1.4.1.14988.1.1.1.2.1.1"
Values ".1.3.6.1.4.1.14988.1.1.1.2.1.8"
Type "bitrate"
Table true
InstancePrefix "ap-rx-"
Instance ".1.3.6.1.4.1.14988.1.1.1.2.1.1"
Values ".1.3.6.1.4.1.14988.1.1.1.2.1.9"